Main menu

Typical Front Access System 50 Switchboard Sections

Type tested switchboard sections to NGTS 3.12.3 Issue 7 June 2006

The sections show below are commonly used and type tested assemblies, but the flexibility of our System 50 design means there are many more variations and configurations available. 

Cabling and maintenance access is from the front of the switchboard. Cable entry is through the bottom of the switchboard cubicles. Section height is 2250mm. Section depth is 630mm. Sections are fitted with 4 off, removable lifting eye bolts for delivery.

 

Side view, front access switchboard

Side view, front access switchboard

Incoming sections in combinations of 600 wide. Max incoming rating 1600A

Incoming sections in combinations of 600 wide. Maximum incoming rating 1600A

Typical section weight600

Double stack of outgoing switches with cable way either side. Max total outgoing rating 1400A. Max outgoing switch rating 200A

Double stack of outgoing switches with cable way either side. Maximum total outgoing rating 1400A. Maximum outgoing switch rating 200A

Typical section weight400 

Section with two outgoing switches up to 400A.

Two outgoing 400A switches

Typical section weight300

Single stack of outgoing switches. Cable way to the lef. Max total outgoing rating 1400A. Max outgoing switch rating 200A.

Single stack of outgoing switches. Cable way to the left. Maximum total outgoing rating 1400A. Maximum outgoing switch rating 200A.

Typical section weight330

Single stack of outgoing switches. Cable way to the right. Max total outgoing rating 1400A. Max outgoing switch rating 200A.

Single stack of outgoing switches. Cable way to the right. Maximum total outgoing rating 1400A. Maximum outgoing switch rating 200A.

Typical section weight330

Outgoing 800A switch section.

Outgoing 800A switch section.

Typical section weight330

Combination section with one 400A and three 200A switches.

Combination section showing one 400A and three 200A switches.

Typical section weight330

WeightAny weights specified are for guidance purposes only. Actual section weight is dependant on final section contents.