Main menu

Typical Rear Access System 50 Switchboard Sections

Type tested switchboard sections to NGTS 3.12.3 Issue 7 June 2006

The sections show below are commonly used and type tested assemblies, but the flexibility of our System 50 design means there are many more variations and configurations available. 

Cabling and maintenance access is from the rear of the switchboard with a minimum recommended access of 1m. Cable entry is through the bottom of the switchboard cubicles. Section height is 2250mm. Section depth is 800mm. Sections are fitted with 4 off, removable lifting eye bolts for delivery.

 

800dSideView

Side view, rear access switchboard

800dIncomingSection

Incoming sections in combinations of 600 wide. Maximum incoming rating 1600A

Typical section weight910

800dDoubleStackOutgoingSection

Double stack of outgoing switches. Maximum total outgoing rating 1400A. Maximum outgoing switch rating 200A

Typical section weight400 

800dSingleStack400AOutgoingSection

Two outgoing 400A switches

Typical section weight280

800dSingleStackOutgoingSection

Single stack of outgoing switches. Maximum total outgoing rating 1400A. Maximum outgoing switch rating 200A.

Typical section weight300

800dCombined800AOutgoingSection

Combined outgoing section. Upper switches <200A. Lower switch <800A.

Typical section weight300

800dCombined400AOutgoingSection

Combined outgoing section. Upper switches <200A. Lower switch <400A.

Typical section weight280

WeightAny weights specified are for guidance purposes only. Actual section weight is dependant on final section contents.